Sale!

DC Solar Spd Surge Protective Device

$4.37

G2040 PV Type 2PV Surge Protective Devices
Innovative tripping and breaking technology
Pressing the contacts on both sides of the module can be easily plugged and unplugged,and can be replaced without interrupting the system operation
Scan the QR code on the base to check the date of manufacture,test data.etc
Category:
Data Download

Description

Main Technical Performance Indicators

TypeG2040PV
 SPD according to EN 61643-31/1EC 61643-31Type 2/Class II/T2
Max. PV voltage (d.c.)(Ucpv )300V dc500V dc600V dc800V dc1000V dc1200V dc1500V dc
In(8/20μs )(KA)20
Imax(8/20μs)(KA )40
Total lighting current(8/20μs) DC+,DC–PE (Imax) 丨total 2P:80kA  3P:120kA
 Voltage protection level (Up)≤1.5kV ≤2.5kV ≤2.5kV  ≤3.2kV ≤4.0kV≤4.0kV≤4.5kV
Response time(tx)25ns
Operating temperature range(TU) -40℃……+80℃
Operating state / fault indicationGreen:normal Red:invalid
Number of ports1
For mounting on35 mm DIN rails acc. To EN60715
Place of installationindoor installation
IP GradeIP20
Weight2P:240g,3P:360g

Surge Protective Devices Product Structure Diagram

Model selection

TypeG2040PV/300G2040PV/500G2040PV/600G2040PV/800G2040PV/1000G2040PV/1200 G2040PV/1500
Ordering number2P:122 1202P:122 122
3P:122 132
2P:122 124
3P:122 134
2P:122 126
3P:122 136
2P:122 128
3P:122 138
2P:122 130
3P:122 140
3P:122 142
Type(Remote signal monitoring)G2040PV/300-FM G2040PV/500-FMG2040PV/600-FMG2040PV/800-FMG2040PV/1000-FMG2040PV/1200-FMG2040PV/1500-FM
Ordering number(Remote signal monitoring )2P:122 1212P:122 123
3P:122 133
2P:122 125
3P:122 135
2P:122 127
3P:122 137
2P:122 129
3P:122 139
2P:122 131
3P:122 141
3P:122 143
Basic Circuit Diagram
Standard Configuration

Dimension Drawing

Any need please contact us