item |
LYV-CD8 |
LYV-CD16 |
LYV-CD24 |
Maximum number of access ways |
8 |
16 |
24 |
working temperature |
-35~+40℃ |
working humidity |
0~80% |
Extreme working height |
3000m |
Maximum input current of each circuit |
DC15A |
Maximum open circuit current of each circuit |
DC1500V |
Fuse |
The positive and negative poles of each circuit are respectively connected with DC1500V PV special fuse |
Whisker |
The positive and negative poles of the current are respectively connected to the special lightning arrester for photovoltaic. |
Circuit breaker |
The positive and negative electrodes of the bus are respectively connected to the photovoltaic special circuit breaker, with a rated current of 160A and a voltage of DC1500V |
Combiner box design |
Closed box design, anti-static, shock proof, dust-proof, rust proof, rain penetration proof, flame retardant |
Heat dissipation of combiner box |
Natural heat dissipation of the box |
Lightning protection of combiner box |
Lightning protection combiner box grounding lightning protection |
Insulation |
Input to ground, output to ground and input to output insulation resistance≥50MΩ
|
Response time |
1s |
Working power |
Use the internal DC power supply |
Test accuracy |
Photovoltaic cell measurement accuracy: 0.5 |
IP Grade |
IP65,Indoor and outdoor installation and use |